Protections | 11 - Performance table79 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
11 - Performance table
General notes:
The performance values given in the next table are valid with Δ 100 ms trip time, temperature and signals
within the operating limits; failure to comply with these limitations could lead to an increase in the tolerances.
Ekip Touch sends the TRIP command if the signal read exceeds the threshold for longer than the set time
(or the time resulting from the calculation formula)
With an inverse time-delay trip curve, the calculation refers to a signal with a constant value throughout
the timing: variation of the alarm signal causes a different trip time
The additional notes are given after all the tables
Standard Protections
Protection
[ANSI code]
Trip time t
t
(1)
Trip threshold
tolerance
(3)
Trip time tolerance
L [49]
(with curve t = k / I
2
)
Activation for If within
range: (1.05 to 1.2) x I1
with If 6 In: ± 10 % /
with If > 6 In: ± 20 %
(with curves 60255-151)
S [50TD / 51]
t
t
= t2 ( with curve t = k )
with If 6 In: ± 7 % /
with If > 6 In: ± 10 %
The best between
± 10% and 40 ms
(with curve t = k / I
2
)
with If 6 In: ± 15 % /
with If > 6 In: ± 20 %
S2 [50TD] t
t
= t5
with If 6 In: ± 7 % /
with If > 6 In: ± 10 %
The best between
± 10% and 40 ms
I [50] t
t
30 ms ± 10 % --
G [50N TD / 51N]
t
t
= t4 ( with curve t = k )
± 7 %
The best between
± 10% and 40 ms
(2)
(with curve t = k / I
2
)
± 15 %
MCR t
t
30 ms ± 10 % --
2I [50] t
t
30 ms ± 10 % --
IU [46] t
t
= t6 ± 10 %
with t6 5 s: ± 100 ms /
with t6 < 5 s the best between
± 10 % and ± 40 ms
Startup
Protection
[ANSI code]
Trip time t
t
Trip threshold
tolerance
(3)
Trip time tolerance
S StartUp t
t
= t2 startup
with If 6 In: ± 7 % /
with If > 6 In: ± 10 %
The best between
± 10% and 40 ms
I StartUp t
t
30 ms ± 10 % --
G StartUp t
t
= t4 startup ± 7 %
The best between
± 10% and 40 ms
S2 StartUp t
t
= t5 startup
with If 6 In: ± 7 % /
with If > 6 In: ± 10 %
The best between
± 10% and 40 ms