EasyManua.ls Logo

ABB SACE Tmax XT5 - Ekip Signalling 2 K

ABB SACE Tmax XT5
205 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB | SACE Tmax XT
External accessories | 13 - Ekip Signalling 2K161 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
13 - Ekip Signalling 2K
Ekip Signalling 2K is an accessory signaling module allowing programmable inputs/outputs to be managed.
This module has:
two contacts for output signals and relative status led
two digital inputs and relative status led
a Power led with the startup status of the module
Accessories Ekip Cartridge and Ekip Supply are required in order to connect Ekip Signalling 2K to Ekip Touch
(page 130, 131).
Models
Three different Signalling 2K modules are available: Ekip Signalling 2K-1, Ekip Signalling 2K-2 and Ekip
Signalling 2K-3.
The modules are identical in terms of characteristics and installation methods, except for: display menus,
cabling and addresses for system communication, which are specific for each module.
NOTE: if different indications are not given, the information in the next chapter is valid for all
three models
The three modules can be connected at the same time to Ekip Touch so as to expand the potential of the unit
(e.g. to increase the number of control outputs and inputs).
IMPORTANT: each Ekip Touch can be fitted with only one module per type. The
configuration with two or three modules of the same model is not allowed (example:
two Ekip Signalling 3T-3 modules)
Connections
For references about the connection and terminals, please consult document 1SDM000005A1001; use AWG
22-16 cables with 1.4 mm maximum outer diameter for the external cabling.
To connect the module to Ekip Supply and Ekip Cartridge, please consult document 1SDH002009A1503.
Power supply
Ekip Com Signalling 2K is supplied directly by the Ekip Supply module to which it is connected.
NOTE: communication between Ekip Touch and the module is interrupted in the absence of
auxiliary power supply
Input
Ekip Touch can be configured so that the status of the inputs corresponds to actions or signals, with different
programming options (page 162).
The connection of each input (H11 and H12 for model 2K-1, H21 and H22 for model 2K-2, H31 and H32 for
model 2K-3) must be made with reference to the common contacts (HC).
The module permits two logic statuses, interpreted differently by Ekip Touch depending on the configuration
selected for each contact:
State Electrical condition Contact configuration
Status detected
by Trip unit
Open Circuit open
Active open ON
Active closed OFF
Closed Short-circuit
Active open OFF
Active closed ON

Table of Contents