152 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A External accessories | 10 - Ekip Com IEC 61850
Remote configurations
Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Preferred configuration
file
If several configuration files are present, allows file hierarchy between
.cid and .iid to be defined
.cid
Enable IEEE 1558
Allows the IEEE 1588 protocol for distribution of the clock and
synchronization signal to be enabled
(1)
.
OFF
IEEE 1558 Master
Enables the module to be set up as a master in the the network
segment to which it belongs (synchronization clock).
OFF
IEEE 1558 Delay
mechanism
Allows the data exchange mode between module and master, either
Peer-to-Peer or End-to-End, to be selected.
End-to-
End
Time zone Defines the time zone to be used for synchronism +00:00
Daylight Saving Time
Used to select whether daylight saving time is present (ON) or not
(OFF) in the country to which the synchronization time refers
OFF
TFTP Security level
Defines the file loading procedure:
TFTP always On = port open, loading always possible
TFTP enable required = port normally closed. To start loading,
Enable TFTP must be run at the start of the procedure and Disable
TFTP must be run at the end of the procedure (disable not necessary,
security command).
TFTP
always On
CB Open/CB Close
command
Defines the limitations to remote opening and closing command
execution:
Standard commands = standard commands (unrestricted) activated
CB operate request = standard commands not activated. Use
programmable functions YC COMMAND and YO COMMAND, and
Request breaker open (28) and Request breaker close (29) commands
Standard
commands
Falg word hex Sets a filter on the selectivity statuses 0
Remote information
Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information Description
HW and Boot version General module information
Flash CRC status and result Information about the correctness of the SW in the module
Ekip Link status Signals Ethernet cable connection errors
SNTP Server Error Error in communication with SNTP server
SNTP Server Synchronization State of synchronism with SNTP server
IEEE 1558 status
Valid with Master IEEE 1588= ON, notifies the presence (Slave or PTP
Master Active) or absence (PTP Master but Passive) of a higher level
master
GOOSE Missing Signals that an expected GOOSE has not been received
Configure Mismatch
A GOOSE received does not conform to the expected structureDecode Error
Sequence number error
Remote programmable statuses
(from E to R)
Condition (true/false) of the programmable states and information on
selectivity arising from logic defined in the configuration files loaded in
module IEC 61850
Zone selectivity remote inputs