ABB | SACE Tmax XT
Protections | 11 - Performance table81 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Motor protections
Protection
[ANSI code]
Trip time t
t
Trip threshold
tolerance
(3)
Trip time tolerance
R JAM [51LR] t
t
= tj ± 10 % with If 6 In: ± 7 % / with If > 6 In: ± 10 %
R STALL [51LR] t
t
= ts ± 10 % ± 10 %
UC [37] t
t
= tuc ± 15 % ± 20 %
U t
t
= tu
(8)
± 15 % ± 20 %
Note on protections
(1)
use trip and threshold current values expressed in In for calculating t
t
(example: If = 0.8 In, I1= 0.6 In)
(2)
with t4 = instantaneous, the maximum tolerance is 50 ms
(3)
Tolerance values valid with Trip unit at steady state or on with auxiliary power supply, trip time 100 ms,
temperature and signals within operating limits; the tolerances in the table after the notes are applicable if the
conditions are not guaranteed
(4)
the trip unit considers a 3% hysteresis for clearing from the alarm condition
(5)
tolerance valid for frequencies within range: fn ± 2 %. A ± 5% tolerance is applicable for off range
frequencies
(6)
± 20% for threshold 0.4 Hz / s
(7)
time to be considered valid after Motor start-up
(8)
time to be considered valid with protection in alarm status after Motor start-up; if the alarm appears during
Motor start-up, the trip unit calculates and uses the lowest value between tu and the half of Motor start-up
Performance guaranteed in all operating conditions
Protection Trip threshold tolerance Trip time tolerance
L Activation within range: (1.05 to 1.2) x I1 ± 20 %
S ± 10 % ± 20 %
I / 2I ± 15 % 60 ms
G ± 15 % ± 20 % (60 ms with t4 = instantaneous)
UF / UF2 / OF /
OF2
± 2 % ± 20 %
Other -- ± 20 %