EasyManuals Logo

ABB SafePlus User Manual

ABB SafePlus
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #8 background imageLoading...
Page #8 background image
8
4. TECHNICAL DATA
4.1 ELECTRICAL DATA SAFERING
4.2 ELECTRICAL DATA SAFEPLUS
SafeRing
C-module
F-module V-module
Switch
disconnector
Earthing switch
Switch-fuse
combination
Earthing switch
Vacuum
circuit-breaker
Earthing switch
Rated voltage kV 12/17,5/24 12/17,5/24 12/17,5/24 12/17,5/24 12/17,5/24 12/17,5/24
Power frequency withstand voltage kV 28
6)
/38/50 28
6)
/38/50 28
6)
/38/50 28
6)
/38/50 28
6)
/38/50 28
6)
/38/50
Impulse withstand voltage kV 95/95/125 95/95/125 95/95/125 95/95/125 95/95/125 95/95/125
Rated current A 630/630/630 200
1)
200/200/200
Breaking capacities:
active load A 630/630/630
closed loop A 670/670/670
off load cable charging A 141/141/141
off load transformer A 20/20/20
earth fault A 205/160/160
earth fault cable charging A 117/91/91
short-circuit breaking current kA see
2)
16/16/16
Making capacity kA 52,5/40/40 52,5/40/40 see
2)
12,5/12,5/12,5 40/40/40 40/40/40
Short time current 0,5 sec
3)
kA 16/16/16
Short time current 1 sec
4)
kA 5/5/5 16/16/16
Short time current 3 sec
5)
kA 21/16/16 21/16/16 16/16/16
1)
Depending on the current rating of the fuse-link
2)
Limited by high voltage fuse-links
3)
Maximum rating for bushings Interface A (200 series plug-in)
4)
Maximum rating for bushings Interface B (400 series plug-in)
5)
Maximum rating for bushings Interface C (400 series bolted)
6)
GOST version is available with 42kV power frequency withstand voltage
SafePlus
C-module F-module V-module V20/V25 module
Switch
disconnector
Earthing
switch
Switch-fuse
combination
Earthing switch
Vacuum
circuit-
breaker
Earthing
switch
Vacuum
circuit-
breaker
Earthing
switch
Rated voltage kV 12/17,5/24 12/17,5/24 12/17,5/24 12/17,5/24 12/17,5/24 12/17,5/24 12/24 12/24
Power frequency withstand voltage kV 28
1)
/38/50 28
1)
/38/50 28
1)
/38/50 28
1)
/38/50 28
1)
/38/50 28
1)
/38/50 28
1)
/50 28
1)
/50
Impulse withstand voltage kV 95/95/125 95/95/125 95/95/125 95/95/125 95/95/125 95/95/125 95/125 95/125
Rated current A 630/630/630 200
2)
630/630/630 630/630
Breaking capacities:
closed loop A 650/650/650
off load cable charging A 140/140/140
off load transformer A 20/20/20
earth fault A 205/160/160
earth fault cable charging A 117/91/91
short-circuit breaking current kA see
3)
21/16/16 25/20 25/20
Making capacity kA 65/52,5
4)
/52,5 62,5/52,5
4)
/50 see
3)
12,5/12,5/12,5 52,5/40/40 52,5/40/40 65/50 62,5/50
Short time current 0,5 sec
5)
kA 16/16/16
Short time current 1 sec
6)
kA 25/-/- 25/-/- 5/5/5 16/16/16 25/21 25/21
Short time current 3 sec
7)
kA 25/21
4)
/21 25/21
4)
/21 21/16/16 21/16/16 25/21 25/21
1)
GOST version is available with 42kV power frequency withstand voltage
2)
Depending on the current rating of the fuse-link
3)
Limited by high voltage fuse-links
4)
Tested at 15,2 kV
5)
Max. rating for bushings Interface A (200 series plug-in)
6)
Max. rating for bushings Interface B (400 series plug-in)
7)
Max. rating for bushings Interface C (400 series bolted)

Table of Contents

Other manuals for ABB SafePlus

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB SafePlus and is the answer not in the manual?

ABB SafePlus Specifications

General IconGeneral
Rated voltageUp to 24 kV
Rated currentUp to 1250 A
Insulation mediumSF6 gas
Rated Lightning Impulse Withstand Voltage125 kV
StandardsIEC 62271-200
DimensionsVaries by configuration
WeightVaries by configuration
Short-time withstand currentUp to 25 kA

Related product manuals