5. INSTALLATION
NOTE
The floor must be well leveled and the unit must be
fixed by means of anchor bolts in accordance with
the dimensional drawing for the number of modules
or units as appropriate.
The tolerance of the evenness is maximum 1 mm per meter.
Unit A B C
1-way 298 337 371
2-way 623 662 696
3-way 948 987 1021
4-way 1273 1312 1346
5-way 1598 1637 1671
5.1 STANDARD 3-WAY SWITCHGEAR
NOTE
The tools required for installation and maintenance
of the switchgear are specified in the tool list in
chapter 20.6.