Table 2: Options available for the added stream
Voltage Module Voltage Module Description
Four voltages and four currents
are added to the stream
x Four voltages and four invalid
currents are added to the
stream
x Four currents and four invalid
voltages are added to the
stream
SAM600 modules for current and voltage measurements can be merged by selecting the
required SAM600 modules from the respective fields, see Figure 27.
IEC18000657 V1 EN-US
Figure 27: PCM600: Selecting Voltage and/or current modules for merging
Define external SV Stream
A SAM600 system has the capability to subscribe any external IEC/UCA 61850-9-2LE
sample value stream on any port. Those external streams can be published on any other
available SAM600 port, called bridging.
To add a sample value stream, right click on the Source Port tab. A stream with default
name is added into the system, see
Figure 28.
IEC18000658 V1 EN-US
Figure 28: Add SV Stream in Source Port Assignment
Configure the SV streams that need to be bridged.
1MRK 511 433-UEN B Section 5
SAM600 Engineering
SAM600 Process Bus I/O System 29
Engineering manual
© Copyright 2017 ABB. All rights reserved