IEC18000659 V1 EN-US
Figure 29: Define SV Streams
SMVID
- The sampled value ID of the stream to be bridged. The minimum length of SMVID
is 10 characters and maximum length is 34 characters.
Source Port
- The SAM600 system port the bridged stream shall be subscribed.
There are two stream types available, see Figure 29.
F4000S1I4U4
- This stream carries 4000 9-2 samples per sec with 50Hz system
frequency. It carries four current and four voltage samples.
F4800S1I4U4
- This stream carries 4800 9-2 samples per second with 60Hz system
frequency. It carries four current and four voltage samples
A SAM600 module cannot receive more than eight bridged streams
either to a single port or to a different ports.
Port Assignment
- In the Destination Port assignment tab, the ports of SAM600
streams and streams which are bridged through a SAM600 system are defined, see
Figure 30.
IEC18000660 V1 EN-US
Figure 30: PCM600: Define publishing ports between the streams and the SAM600
modules
A SAM600 module cannot use more than eight source streams for its
configured sent streams. For more details, see
SAM600 Operation manual
.
A SAM600 module can be configured to send up to 10 streams.
Section 5 1MRK 511 433-UEN B
SAM600 Engineering
30 SAM600 Process Bus I/O System
Engineering manual
© Copyright 2017 ABB. All rights reserved