1 - 16 WBPEEUI240751C0
Specifications
Specifications
Tables 1-8 through 1-10 are general I/O and auxiliary block
specifications.
NOTE: Refer to the Harmony I/O data sheets (Table 1-4) for current consump-
tion and heat dissipation specifications.
CE Mark directives 73/23/EEC Low voltage directive
89/336/EEC EMC directive
92/31/EEC
90/683/EEC CE marking directives
93/68/EEC
93/465/EEC
Certifications CSA Certified for use as process control
equipment in an ordinary (nonhazardous)
location
Factory Mutual (FM) Approved for use in Class I; Di vision 2 ;
Groups A, B, C, D; hazardous locations.
SUBJECT TO CHANGE WITHOUT NOTICE
Table 1 -7. Des ign Standards
(continued)
Category Standard Description
Table 1 -8. General I/O Blo ck Specifications
Property Characteristic/Value
1
I/O blocks
(Refer to indicated table for
individual block specifications)
Microprocessor 16-bit processor running at 16 MHz
Memory 64 kb SRAM
512 kb flash ROM
Redundancy link data rate 1 Mbaud
Block logic power (BLP) 21.6 VDC m inimum
24.0 VDC nominal
28.0 VDC maximum
Block Refer To Block Refer To
AIN-120 Table 2-1 CIO-100 Table 2-7
AIN-200 Table 2-2 DIO-400 Table 2-9
AIN-220 Table 2-3 DOT-100 Table 2-10
AIN-300 Table 2-4 DOT-120 Table 2-11
AOT-150 Table 2-5