WBPEEUI240751C0 1 - 17
Field power (IFP/LFP) 24.0 VDC nominal
48.0 VDC nominal
125.0 VDC nominal
120.0 VAC nominal
240.0 VAC nominal
LFP terminals 3.0 A
Fusing Refer to the individual block specifications in Section 2
Common mode isolation
2
Tes te d
300 VDC/V
RMS
at 60 Hz
1,400 V
RMS
at 60 Hz for 2 sec
Differential input voltage without
damage
±15 VDC/V
RMS
continuous
Common mode voltage
3
±5 VDC/V
RMS
continuous
Input/output protection Continuous short to ground - protected with current limiting
Dimensions
Overvoltage (installation) category ANSI/ISA-S82.01-1994 and IEC 1010-1
Iforcircuitsabove150V
II for circuits below 150 V
NOTES:
1. All specification values are maximums unless stated otherwi se.
2. Applies only to blocks with isolated input and output channels. Refer to Section 2 to determine if a block has isolated channels.
3. Applies only to blocks with nonisolated input and output channels. Refer to Section 2 to determine if a block has isolated
channels.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTI CE
Table 1 -8. General I/O Blo ck Sp ecifications
(continued)
Property Characteristic/Value
1
Type
Height Width Depth
mm in. mm in. mm in.
I/O module 266 10.5 76 3.0 162 6.4
Nonredundant base 267 10.5 138 5.4 169 6.7
Redundant base 267 10.5 217 8.5 169 6.7
NOTE:RefertoAppendix A for hardware drawings.
Table 1 -9. General Auxiliary Block Specifications
Property Characteristic/Value
Auxiliary blocks
(Refer to indicated table for
individual block specifications)
Block Refer To
CIO-110 Table 2-8
RLY-100 Table 2-12
RLY-200 Table 2-13