EasyManua.ls Logo

ABB Symphony Harmony Series - Block

ABB Symphony Harmony Series
402 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PR14 - 2 WBPEEUI240751C0
Procedure
4. Remove the access cover from the left side of the I/O mod-
ule (Fig. PR14-1).
5. Set the readback/fusing select jumpers as appropriate
(Table PR14-2). Refer to Figure PR14-2 for the jumper
locations.
The jumper settings determine which of the contact outputs
are monitored. Both readback jumpers n-J1 and n-J2 must
mustmust
must be
set the same. For example, if the output is wired as a normally
closed output, then both jumpers should be in the normally
closed position. If both contact outputs are used, only one is
monitored depending on the jumper settings.
6. Replace the access cover.
7. Verify 6.3 A, 250 V fuses are present in each of the
DOT-120 block fuse holders XF1 through XF16 (Fig. PR14-2).
8. Verify 1.6 A, 250 V fuses are present in both the A and B
channel block power fuse holders on the I/O module.
Table PR14-1. F ield Power Se lect Jumpers
Field Power
1
J1 J2 Description
IFP Field power from mounting
column bus
LFP Field power from LFP
terminals on base
NOTE:
1. 24 VDC to power output relay coils.
123 123
123 123
Table PR14-2. Readback/Fusing Select Jump ers
Output n
1
-J1 n
1
-J2
Normally closed
Normally open
NOTE:
1. n corresponds to the channel number from 1 to 16. For example,
1-J1 and 1-J2 co nfigure channel one.
1
2
3
1
2
3
1
2
3
1
2
3

Table of Contents

Other manuals for ABB Symphony Harmony Series

Related product manuals