WBPEEUI240751C0 PR15 - 1
PR15
CIO-110 Setup
Purpose/Scope
This procedure gives the steps required to set up the CIO-110
block for proper operation.
Parts
None.
To o l s
• Small-tipped, flat-blade screwdriver.
• Needlenose pliers (optional).
• IISAC01 Analog Control Station instruction.
Procedure
□
1. Set the M/A power select jumpers J1 and J2 as appropri-
ate (Table PR15-1).
Refer to Figure PR15-1 for jumper locations. Refer to the
IISAC01 Analog Control Station
IISAC01 Analog Control StationIISAC01 Analog Control Station
IISAC01 Analog Control Station instruction for an explanation
of the M/A power.
□
2. Verify a 1.6 A, 250 V fuse is present in fuse holder XF3.
This fuse is required when using LFP power for M/A power.
□
3. Verify 4.0 A, 250 V fuses are present in fuse holders XF1
and XF2. These fuses are for the +24 VDC LFP power that
operates IISAC01 control stations connected at P2 and P4
respectively.
5 min.
Table PR15-1. M /A Power Select Jumpers
Power Source J1 J2
External M/A power source connected at
terminal block
LFP power used for M/A power; no external
M/A power source connected
123
456
123
456
123
456
123
456