Digital Output
WBPEEUI240751C0 4 - 9
Digital Output
For digital output capable blocks, channels are directly wired
in parallel to both I/O modules (Figs. 4-9 through 4-12). A
short across an output of one I/O module due to an I/O block
fault will not allow the output to switch off. There are no
detectable channel failures for the digital outputs of DIO-400
and DOT-100 blocks.
The DOT-120 block has readback circuitry to monitor actual
outputs. If there is a difference between the actual output and
the read back output, the channel will be marked as suspect.
For the DOT-120 block, failover will occur if the primary I/O
module has an output stuck closed, but the backup will be
unable to correct this condition.