AIN-200
WBPEEUI240751C0 2 - 3
The AIN-200 block supports 16 isolated input channels that
operate in voltage mode only. Each input channel is individu-
ally software configurable for voltage range or thermocouple
type. Cold junction compensation for thermocouple inputs is
included. The block supports redundant I/O electronics.
Table 2-2. AIN -200 Specific ations
Property Characteristic/Value
1
Input range –10 to +10 VDC
–100 to +100 mVDC
Thermocouple types B, E, J, K, L, N (14 AWG), N (28 AWG), R, S, T, U
Chinese E, S
Channels 16 isolated
Input impedance 10 MΩ minimum
Full scale range 20 V or 200 mV
Maximum error
2
±0.05% of full scale range
Temperature effect (0° to 70°C) ±0.005%/°C
Settling time per channel
(100% step change)
170 msec to 95% of final value
Update rate
3
All channels 18 times per second (56 msec)
Rejection (50-60 Hz)
Normal mode
Common mode
–70 dB
–120 dB
Number of A-to-D converters 16 + 1 for cold junction
Full scale reso lution 18 bit resolution for –10 to +10 VDC range or –100 to
+100 mVDC range
BLP fuse (A and B) 1.6 A, 250 V, 5 x 20 mm, fast-acting, low break capacity
(IEC 127-2/II)
IFP/LFP fuse 3.15 A, 250 V, 5 x 20 mm, time-lag, medium break capacity
(IEC 127-2/VI)
Weight
Module
Nonredundant base
Redundant base
1.0 kg (2.2 lb)
1.2 kg (2.7 lb)
1.6 kg (3.4 lb)
NOTES:
1. All specification values are maximums unless stated otherwi se.
2. Maximum error includes effects of nonlinearity, repeatability, hysteresis, noise, and quantization error.
3. This is the rate at which the block reads and updates values. The rate at which the values are actually read and become avail-
able to the system depends on the scan cycle of the controller.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTI CE