2 - 14 WBPEEUI240751C0
DIO-400
In Turn ON voltage
24 VDC
48 VDC
125 VDC
120 VA C
240 VA C
19.5 VDC minimum
39 VDC minimum
95 VDC minimum
85 VAC minimum
190 VA C minimum
Tur n O F F vol t ag e
24 VDC
48 VDC
125 VDC
120 VA C
240 VA C
12 VDC
18 VDC
58 VDC
40 VAC
87 VAC
ON current
3
4.6 to 7.3 mA typical
OFF leakage current <1.5 mA
Fault currents per channel
24 VDC
48 VDC
125 VDC
120 VA C
240 VA C
Each channel provides current limiting and automatic recovery
31 mA nominal
8.1 mA nominal
14 mA nominal
15 mA nominal
15 mA nominal
Out Open collector
Update rate All channels 83 times per second (12 msec)
Switching speed <0.25 msec
OFF leakage current <1 mA
BLP fuse (A and B) 1.6 A, 250 V, 5 x 20 mm, fast-acting, low break capacity
(IEC 127-2/II)
IFP/LFP fuse 3.15 A, 250 V, 5 x 20 mm, time-lag, medium break capacity
(IEC 127-2/VI)
Weight
Module
Nonredundant base
Redundant base
1.0 kg (2.2 lb)
1.3 kg (2.9 lb)
1.7 kg (3.7 lb)
NOTES:
1. All specification values are maximums unless stated otherwise.
2. Software selectable in 1-msec increments up to 255 msec (debounce period).
3. Actual input current depend s on inp ut type selection.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIC E
Table 2 -9. DIO-400 Specifications
(continued)
Property Characteristic/Value
1
Output Off On Load
24 VDC 28 VDC 2.5 VDC 250 mA
48 VDC 56 VDC 2.5 VDC 250 mA