RLY-200
WBPEEUI240751C0 2 - 19
Table 2-13. RLY-200 Specifications (Solid State Relays)
Property Characteristic/Value
1
Outputs 24 VDC, 125 VDC
120 VA C, 240 VAC
Channels 8
Relays
Relay fusing
Field power (IFP/LFP)
voltage
4
24.0 VDC nominal
Weight (with relays) 1.8 kg (4.0 lb)
NOTES:
1. All specification values are maximums unless stated otherwi se.
2. AC
RMS
current.
3. AC
PEAK
current.
4. 24 VDC from DIO block to power relay coils.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTI CE
Property 24 VDC 125 VDC 120/240 VAC
Output range (VDC/VAC) 5 to 60 10 to 200 12 to 280
Output current (A)
2
:
0° to 30°C (32° to 86°F)
15° to 25°C (59° to 77°F)
at 70°C (158°F)
—
3.0
1.2
—
1.0
0.4
—
3.0
1.2
Load frequency (Hz) — — 47 to 63
Leakage current (mA)
2
0.01 0.01 0.75
One cycle surge (A)
3
5.0 1.5 85.0
Relay Fuse Description
24 VDC 3.15 A, 250 V 5 x 20 mm, fast-acting, low break capacity
(IEC 127-2/II)
125 VDC 1.0 A, 250 V 5 x 20 mm, fast-acting, low break capacity
(IEC 127-2/II)
120 VAC 3.15 A, 250 V 5 x 20 mm, time-lag, high break capacity
(IEC 127-2/V)
240 VAC