Field Device Connection
WBPEEUI240751C0 PR12 - 5
□
10. Verify 1.6 A, 250 V fuses are present in both the A and B
channel block power fuse holders on the I/O module.
□
11. Verify a 3.15 A, 250 V fuse is present in the field power fuse
holder.
□
12. If installing redundant I/O modules, insure the settings for
both I/O modules are the same.
Field Device Connection
Figures PR12-3 and PR12-4 show the circuit connections
made after attaching field wiring and setting jumpers.
Figure PR12-5 shows the circuit connections made when oper-
ating the DIO-400 block with an RLY-100 or RLY-200 block.
Figure PR12-1. Configuration Jumper Access
T00914A
ACCESS
COVER
I/O B O A RD