30 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. E
… 10 Commissioning
… Communication
PROFIBUS® Communication
Note
The PROFIBUS PA® protocol is an unsecured protocol, as such
the intended application should be assessed to ensure that
these protocols are suitable before implementation.
The interface complies with Profile 3.01
(Standard PROFIBUS®, EN 50170, DIN 1924 [PRO91]).
1 Transmitter
2 Bus termination
3 Segment coupler
4 PC / DCS
Figure 21: Example for PROFIBUS PA® connection
Manufacturer ID 0x1A
ID number 0x3470 [0x9700]
Profile PA 3.01
Configuration On device using LCD indicator
DTM
EDD
GSD
Transmission signal IEC 61158-2
Voltage / current consumption
• Mean current consumption: 12 mA.
In the event of an error, the FDE function (= Fault
Disconnection Electronic) integrated in the device makes
sure that the current consumption cannot exceed a
maximum of 20 mA.
FOUNDATION Fieldbus® Communication
Note
The FOUNDATION Fieldbus® protocol is an unsecured protocol,
as such the intended application should be assessed to ensure
that these protocols are suitable before implementation.
1 Transmitter
2 Bus termination
3 Handheld terminal
4 Linking Device
5 PC / DCS
Figure 22: Example for FOUNDATION Fieldbus® connection
Device ID 000320001F...
ITK 5.x
Configuration On device using LCD indicator
EDD
Transmission signal IEC 61158-2
Voltage / current consumption
• Mean current consumption: 12 mA.
In the event of an error, the FDE function (= Fault
Disconnection Electronic) integrated in the device makes
sure that the current consumption cannot exceed a
maximum of 20 mA.