TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. E 53
Factory settings
Firmware settings
The transmitter is configured at the factory. The table below contains the relevant parameter values.
Menu Designation Parameter Factory setting
Device Setup Write protection – No
Input Sensor 1 Sensor Type Pt100 (IEC60751)
R-Connection Three-wire
Measured Range Begin
1)
0
Measured Range End
1)
100
Engineering Unit Degrees °C
Damping Off
Process Alarm Fault signaling
1)
Overrange 22 mA
1
Input Sensor 2 Sensor Type Off
Input / output assignment Measurement type Sensor 1
TAG – –
HART Burstmode
1
– TIXXX-
1
Display Display Value – Process Variable
Bargraph
1
– Yes, output %
1
Language – German
Contrast – 50 %
Communication HART Burstmode
1
Status
1)
Off
1
Bus Address
2 3
– 126
2
/ 30
3
Simulation mode
3
– Off
3
HART Protocol – HART 5
4
1 Only applies to HART transmitters
2 Only applies to PROFIBUS PA transmitters
3 Only applies to FOUNDATION Fieldbus transmitters
4 HART 7 provided unless specifically specified in the order.