- 121 - UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
FieldBusPlug / Issue: 03.2012
Para-
meter
Number
Parameter Description, Explanations Options Ad-
just-
able
via
22 Checkback Selection of the checkback
supervision method.
Contact DI0 (1),
Current (2),
Simulation (3)
All
86 Inching DI
start input
(Jog)
Enables inching (i.e. jogging)
of the start signal originating
from a digital input.
No (0),
Yes (1)
All
19 Enable custom
logic
Enable the execution of a
customer defined application
No (0),
Yes (1)
All
Local Control Mode 1
90 Loc 1 start
bus cyclic
Allow the motor to be started
via cyclic bus command in
local mode 1
No (0),
Yes (1)
All
91 Loc 1 stop
bus cyclic
Allow the motor to be stop-
ped via cyclic bus command
in local mode 1
No (0),
Yes (1)
94 Loc1 start
LCD
Allow the motor to be started
via LCD panel in local mode
1
No (0),
Yes (1)
95 Loc1 stop
LCD
Allow the motor to be stop-
ped via LCD panel in local
mode 1
No (0),
Yes (1)
96 Loc1 start bus
acyclic
Allow the motor to be started
via acyclic bus command in
local mode 1 (e.g. from DTM)
No (0),
Yes (1)
97 Loc1 stop bus
acyclic
Allow the motor to be stop-
ped via acyclic bus com-
mand in local mode 1 (e.g.
from DTM)
No (0),
Yes (1)
92 Loc1 start DI Allow the motor to be started
via digital input in local mode
1
No (0),
Yes (1)
93 Loc1 stop DI Allow the motor to be stop-
ped via digital input in local
mode 1
No (0),
Yes (1)
Local Control Mode 2
Motor Management Parameters Continued