- 130 -UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
FieldBusPlug / Issue: 03.2012
VI150 / VI155 Parameters
Para-
meter
Number
Parameter
Name
Description, Explanations Options Adjustable via
4 VI15x
Enabled
Specify if the module is con-
nected to UMC
0: Off
1: On
All
158 Nominal Line
Voltage
Line to Line Voltage e.g.
190V, 400V or 690V
U
e
: 150...690V in steps of 1V
Default: 400V
All excluding
GSD-PDQ22
159 U Low Trip
Level
Value in % of U/U
e
. Below
this value a trip is generated.
70 ... 100%
70 disables the function
All excluding
GSD-PDQ22
160 U Low Trip
Delay
Delay time until a low voltage
trip is triggered.
0...25.5s in steps of 0.1s
Default: 3s
Unscaled: 0...255
Example: 20 means 2s
All excluding
GSD-PDQ22
161 U Low Warn
Level
Value in % of U/U
e
. Below
this value a warning is gene-
rated.
70 ... 100%
70 disables the function
All excluding
GSD-PDQ22
162 U Low Warn
Delay
Delay time until a low voltage
warning is triggered.
0...25.5s in steps of 0.1s
Default: 3s
Unscaled: 0...255
Example: 20 means 2s
All excluding
GSD-PDQ22
163 U High Trip
Level
Value in % of U/U
e
. Above
this value a trip is generated.
100 ... 116% of U
e
in steps
of 1%
116% disables the function
All excluding
GSD-PDQ22
164 U High Trip
Delay
Delay time until a high vol-
tage trip is triggered.
0...25.5s in steps of 0.1s
Default: 3s
Unscaled: 0...255
Example: 20 means 2s
All excluding
GSD-PDQ22
165 U High Warn
Level
Value in % of U/U
e
. Above
this value a warning is gene-
rated.
100 ... 116% of U
e
in steps
of 1%
116% disables the function
All excluding
GSD-PDQ22
166 U High Warn
Delay
Delay time until a high vol-
tage warning is triggered.
0...25.5s in steps of 0.1s
Default: 3s
Unscaled: 0...255
Example: 20 means 2s
All excluding
GSD-PDQ22
200 PwrFactor
Trip Level
Power factor (cos phi).
Below this value a trip is
generated.
30 disables the function
0.30 ... 1 in steps of 0.01
Unscaled: 30...100
Example: 75 means a PF
of 0.75
All excluding
GSD-PDQ22
201 PwrFactor
Trip Delay
Delay time until a low power
factor trip is triggered.
0...25.5s in steps of 0.1s
Default: 3s
Unscaled: 0...255
Example: 20 means 2s
All excluding
GSD-PDQ22
202 PwrFactor
Warn Level
Power factor (cos phi).
Below this value a warning is
generated.
30 disables the function
0.30 ... 1 in steps of 0.01
Unscaled: 30...100
Example: 75 means a PF
of 0.75
All excluding
GSD-PDQ22