- 131 - UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
FieldBusPlug / Issue: 03.2012
203 PwrFactor
Warn Delay
Delay time until a low power
factor warning is triggered
0...25.5s in steps of 0.1s
Default: 3s
Unscaled: 0...255
Example: 20 means 2s
All excluding
GSD-PDQ22
204 U Imb. Trip
Level
Voltage imbalance trip level
20 disables the function
0.2 ... 20% in steps of 0.1%
Unscaled 2..200
All excluding
GSD-PDQ22
205 U Imb. Trip
Delay
Delay time until an imalance
trip is triggered
0...25.5s in steps of 0.1s
Default: 1s
Unscaled: 0...255
Example: 20 means 2s
All excluding
GSD-PDQ22
206 U Imb. Warn
Level
Voltage imbalance warning
level
20 disables the function
0.2 ... 20% in steps of 0.1%
Unscaled 2..200
All excluding
GSD-PDQ22
207 U Imb. Warn
Delay
Delay time until an imalance
warning is triggered
0...25.5s in steps of 0.1s
Default: 1s
Unscaled: 0...255
Example: 20 means 2s
All excluding
GSD-PDQ22
208 P Low Trip
Level
Below this value a trip is
generated
20 disables the function
20 ... 100% in steps of 1% All excluding
GSD-PDQ22
209 P Low Trip
Delay
Delay time until an low po-
wer trip is triggered
0...255s in steps of 1s
Default: 5s
All excluding
GSD-PDQ22
210 P Low Warn
Level
Below this value a warning is
generated.
20 disables the function
20 ... 100% in steps of 1% All excluding
GSD-PDQ22
211 P Low Warn
Delay
Delay time until an low po-
wer warning is triggered
0...255s in steps of 1s
Default: 5s
All excluding
GSD-PDQ22
212 P High Trip
Level
Above this value a trip is
generated
200 (1000%) disables the
function
100 ... 1000% in steps of 5%
Unscaled: 20...200
Example: 20 means 100%
All excluding
GSD-PDQ22
213 P High Trip
Delay
Delay time until an high
power trip is triggered
0...255s in steps of 1s
Default: 10s
All excluding
GSD-PDQ22
214 P High Warn
Level
Above this value a warning is
generated
200% (1000) disables the
function
100 ... 1000% in steps of 5%
Unscaled: 20...200
Example: 20 means 100%
All excluding
GSD-PDQ22
215 P High Warn
Delay
Delay time until an high po-
wer warning is triggered
0...255s in steps of 1s
Default: 10s
All excluding
GSD-PDQ22
216 Nominal Po-
wer Factor
Power factor value from the
name plate or data sheet of
the motor
0.01 ... 1 in steps of 0.01
Default: 1
Unscaled: 1...100
Example: 75 means a PF
of 0.75
All excluding
GSD-PDQ22