- 147 - UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
FieldBusPlug / Issue: 03.2012
General
Tightening torque for the communication terminals
Tightening torque for the input, output and supply
terminals
Net weight 0.22 kg
Degree of protection IP20
Temperature range storage -25 ... +70 °C
operation 0 ... +55 °C (DX122) / +60 °C (DX111)
Marks, Approvals CE, cUL
Furher in preparation. Ask your local sales repre-
sentative for other marks/approvals.
Relay Outputs
Number of relay outputs 4
1DO1, 1DO2 with root 1DOC
2DO3, 2DO4 with root 2DOC
Voltage range of contacts 12-250 V AC/DC
Uimp Uimp=4 kV
Short-circuit protection 6 A gG per root (1DOC, 2DOC)
Lowest switched power for correct signals 1 W or 1 VA
0.22 Nm
1 x 0.14 ... 1.5 mm
2
28 ... 16 AWG
1 x 0.14 ... 1.5 mm
2
28 ... 16 AWG
1 x 0.25 ... 0.5 mm
2
28 ... 16AWG
7mm
0.28 in
7mm
0.28 in
7mm
0.28 in
ø 1.5 mm
ø 4,5 mm / 0.177 in / PH
1
2 x 0.5 ... 4 mm
2
2 x 20 ... 12 AWG
2 x 0.75 ... 2.5 mm
2
2 x 18 ... 14 AWG
2 x 0.75 ... 2.5 mm
2
2 x 18 ... 14 AWG
7mm
0.28 in
7mm
0.28 in
7mm
0.28 in
0.6 ... 0.8 Nm
5.31 ... 7.08 in.lb