- 148 -UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
FieldBusPlug / Issue: 03.2012
Relay Outputs
Switching of inductive power Inductive loads need additional measures for
spark suppression. Diodes for DC voltage and var-
istors / RC elements for AC voltage are suitable.
Some DC coil contactors contain rectifiers which
suppress sparks perfectly.
Switching capacity per relay contact acc. to EN
60947-5-1 (electromagnetic load)
AC-15 240 V AC: max. 1,5 A
AC-15 120 V AC: max. 3 A
DC-13 250 V DC max. 0.11 A
DC-13 125 V DC max. 0.22 A
DC-13 24 V DC max. 1 A
Relay contact service life Mechanical 500 000 switching cycles
Electrical (250 V AC):
0.5 A: 100 000 cycles
1.5 A 50 000 switching
Internal clearance and creepage distances of relay
contacts to 24 V circuits
> 5.5 mm (safety insulation up to 250 V AC)
(EN 60947-1, Pollution degree 2)
Pollution degree terminals: 3
Digital Inputs DX111
Number of digital inputs 8 externally supplied, isolated inputs
Type 1 accord. to EN 61131-1
1DI0 ... 1DI4 with common root 1DIZ
2DI5 ... 2DI7 with common root 2DIZ
Supply for digital inputs 24 V DC
Isolation Yes
Input signal bounce suppression Typ. 6 ms
Signal 0 range including ripple -31.2 ... +5 V
Signal 1 range including ripple +15 ... +31.2 V
Input current per channel (24 V DC) Typ. 6.0 mA
Input resistor to 0 V 3.9 k