- 149 - UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
FieldBusPlug / Issue: 03.2012
Digital Inputs DX111
Cable length unshielded max. 600 m
shielded max. 1000 m
Digital Inputs DX122
Number of digital inputs 8 externally supplied, isolated inputs
Type 2 accord. to EN 61131-1
1DI0 ... 1DI4 with common root 1DIZ
2DI5 ... 2DI7 with common root 2DIZ
Supply for digital inputs 110 V AC - 240 V AC
Isolation Yes
Input signal bounce suppression Typ. 20 ms
Signal 0 range including ripple 0 ... 40 V AC
Signal 1 range including ripple 74 ... 265 V AC
Frequency range 45 ... 65 Hz
Input current per channel (230V AC) Typ. 10 mA
Analogue Output
Type of connection 2-wire connection to display e.g. the motor current
on an analogue meter.
Configurable output range 0-10 mA, 0/4 mA - 20 mA, 0-10 V
Cable shielding Recommended for up to 30 m and outside the
switchgear cabinet; shielding mandatory for
cables over 30 m
Max. output voltage 10 V
Accuracy < 5%
Max. output load 500 
Min. output load 1 k
Resolution 8 bit
Short-circuit-proof Yes
Open-wire detection
Short-circuit detection
Yes, if configured as 0/4-20 mA output
Yes, if configured as 0-10V output
Isolation No

Table of Contents