- 88 -UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
FieldBusPlug / Issue: 03.2012
Actuator 4
Open position via torque and limit switches, Closed posi-
tion via limit switch only
DI0
13
24V
12
DI3
16
DI1
14
Open
Torque
Open,
Closed
Closed
2CDC 342 022 F0206
Limit switches
DI0: Preparation for Open limit motor off
DI1: Motor off, start only in Open direction
DI3:
•Motor off if prepared for Open off, start only
in Closed direction
•Fault if not prepared or if during closing
Remark:
•The limit switch Closed prepares the stop.
Torque closed stops the motor. Starting is
only possible in the opposite direction
•The single torque signals in the telegram -
torque Open or torque Closed - are calcu-
lated based on the direction of movement
before the stop.
Definitions and monitoring signals particular to the control functions Actuator 1,2,3 and 4
•Input signals: Open and Closed inputs are active signals, torque input is a closed loop signal.
•The two torque signals are connected in series. The discrete torque signal is created based on the previ-
ous direction of movement.
Remark:
If DI2 is not needed as fault input it can be connected to the link between the torque contacts to find out
which torque signal is active.
•Run-time Open <-> Closed: The Run-time limit (= Star-delta starting time) must be changed and should
be set according to actuator data. Setting the Run-time limit = 1 s disables the supervision.
•Starting from Open or Closed: The limit switch has to open within the start monitoring time of 3 s.
Exceeding the time results in the fault signal Open limit switch 1 -> 0 not occurring within 3 s after the
Closed command. The start monitoring time can be extended.
•A faulty torque signal in the intermediate position sets the internal fault signal. The motor is stopped and
can be started again
- after fault reset via fieldbus or other - AND -
- only in the opposite direction (previous direction is blocked).
After starting the torque signal must disappear within 0.5 s. Otherwise the internal fault signal is set
again. A fault reset and start in the opposite direction can be repeated as often as desired.
•If after powering up a torque signal (0-signal) is present and neither an Open nor a Closed signal is pre-
sent it is presumed that the torque occurred during closing. The motor can be started:
- after fault reset via fieldbus or other - AND -
- only in the Open direction