EasyManua.ls Logo

ABB Uniswitch - Operations in Fixed Mounted Circuit-Breaker Cubicles

ABB Uniswitch
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB
27
Uniswitch Operation and
Maintenance Manual
UNIS14GB 05-02
4.3.1.5 Operations in fixed mounted circuit-breaker cubicles
General To achieve an isolating distance in accordance with specified
requirements a 3-position switch-disconnector with an earthing switch is
mounted between the busbar and circuit-breaker. An EM earthing switch
is connected to the other side of the circuit-breaker (current
transformers and HV-cables).
The switch-disconnector and EM earthing switch are mechanically
connected to the operating device and they are operated simultaneously
between open and earthed position.
Because the switch-disconnector is capable of breaking currents under
normal circuit conditions there is not any need for mechanical interlocks
between the circuit-breaker and switch-disconnector.
Operating sequences:
Earthing the cubicle
Figure 4.5
Operating and signalling
parts of fixed type HD4
circuit-breaker
1) Open the circuit-breaker either electrically or mechanically by push
button (43.1).
2) Open the SFG switch-disconnector (see 4.3.1.2).
3) Close the earthing switches on both sides of the circuit-breaker (see
4.3.1.3).
Operating sequences:
Connecting the cubicle
in the network
1) Open the earthing switches (see 4.3.1.4).
2) Close the switch-disconnector (see 4.3.1.1).
3) Close the circuit-breaker by push button (43.2).

Table of Contents

Related product manuals