6 Troubleshooting
Problem Action
All cubicle types
Switch-disconnector cannot be closed.
Check that the switch is in the open position.
Check that the interlocking selector is in the
‘Operation position.
Turn the operating handle clockwise.
Switch-disconnector cannot be opened.
Check that the switch is in the closed position.
Check that the interlocking selector is in the
‘Operation position.
Turn the operating handle anti-clockwise.
Switch-disconnector cannot be moved to
the earthed position.
Check that the switch is in the open position.
Check that the interlocking selector is in the ‘Test’
position.
Turn the operating handle clockwise.
Switch-disconnector cannot be moved
from the open to earthed position.
Check that the switch is in the earthed position.
Check that the interlocking selector is in the ‘Test’
position.
Turn the operating handle clockwise.
Cable compartment door will not open or
close.
Check that the switch is in the earthed position.
Check that the interlocking selector is in the ‘Door
open position.
Motor operated switch-disconnector
Switch-disconnector will not close or
open.
Check that the switch is not in the earthed position.
Check that the interlocking selector is in the
‘Operation position.
Check that the auxiliary power supply is connected.
Switch-fuse cubicle
Switch-fuse will not close. If the switch is in the open position due to a fuse trip or
motor operation, the notch on the operating shaft is to be
turned downwards before the switch can be operated to
the closed position.
Check to see if a fuse has blown.