The switch-fuse has not operated even
though a fuse has blown.
Check that the fuse is correctly fitted so that the trip pin
indicator is pointing upwards.
Circuit-breaker cubicle
The cable compartment door will not
open.
Check that the switch is in the earthed position.
Check the interlocking selector is in the ‘Door open
position.
Remove the key from the circuit-breaker before
opening or closing the door.
The circuit-breaker will not go to the
closed position.
Ensure that the closing spring is fully charged, and
that the interlocking coil is not energised.
Check that the circuit-breaker key is in place and
turned to the correct operating position.
Check that the circuit-breakers auxiliary voltage plug
is properly locked into the socket.
Check that the control pin is on its position (HAD-
US).
Instrument Transformers
Secondary measurements from the
current transformers are not possible.
Check that all shorting links on the secondary
terminals of the current transformers have been
removed.
Check the connections.