5 - Installation
Connection of the RS485 line
On the inverter models which equip the UNO-DM-COM KIT board it is
possible to use the RS485 communication port for: Integrating the in-
verter with a third party monitoring and control systems; Carrying out
“daisy-chain” (“in-out”) connections of multiple inverters installation; Set-
ting internal inverter paramenters with the dedicated advanced congura-
tion software “Aurora Manager Lite”.
The inverter RS458 communication protocol must be properly congured depending on the
device to which it communicates. The RS485 protocol can be changed through the relevant
section of internal webserver (see the specic chapter) or through the display and the key-
board (see the specic chapter).
The connection of the serial communication cable must be made to the
specic RS485 connector
26
present on the UNO-DM-COM KIT board.
For connection of the RS485 communication line is necessary a three-
wire shielded cable. The cable specications are described in the fol-
lowing table:
Cable type AWG
Characteristic
impedance
Operating
voltage
Operating
temperature
Shielded 22 - 24 120 Ohm ≥300 V -20...+60 °C
-T/R
+T/R
RTN
-T/R
+T/R
RTN
SHIELD
SHIELD
Shield continuity must be provided along the communication line and must be grounded at a
single point. It is recommended not to exceed a length of 1000m for the communication line.
The cabling of the RS485 line must be winded up to the toroidal provided
in the package (1 winding); this toroidal shall be conveniently placed near
the cable gland which is in the bottom part of the inverter.
1 2 3