EasyManua.ls Logo

ABB XRC G5 - Open Transmission Control Protocol (TCP) Ports

ABB XRC G5
145 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21060 26M N AA | X SER IE S
G5
| 77
Table 9-3: User-enabled services on XSeries
G5
Service
Name
Default
state
Description
Security feature available
SSH/SFTP
Service
Disabled
Serves connection requests
for secure login shell and file
transfer. Supports
connection requests from
third-party SSH/SFTP clients
Authentication based on private-public
key pairs, passphrase-protected keys
Totalflow
Software
Update
Service
Enabled
Enables or blocks the ability
of the device loader to
update the embedded
software.
None specific to the service. Must use Bi-
level security passcode or Role-Based
Authentication (RBAC)
9.2.2 Open Transmission Control Protocol (TCP) ports
The table below lists the open TCP ports on an XSeries
G5
device. These ports are used for all TCP/IP
based connections which are supported by the Ethernet and Wi-Fi interfaces.
Protocols over TCP can be standard like SSH, or proprietary like Totalflow (Remote or Local).
Table 9-4: Open TCP ports on an XSeries
G5
Default
TCP port
User-
configurable
Protocol using
the port
Description
9999
Yes
Totalflow/TCP
Assigned to connections used for device
monitoring, configuration and data collection or
polling. PCCU, WinCCU, TDS and third-party SCADA
systems request these connections.
65535
No
Device
Loader/TCP
Assigned to the device loader connections for
device software update.
PCCU requests this type of connection.
9696
No
SSH/TCP
Assigned to secure shell (SSH/SFTP) connections.
Third-party SSH/SFTP clients request these
connections.
502
Yes
Modbus /TCP
Assigned to connections between the XSeries
G5
devices and external Modbus devices for
communication and data transfer
IMPORTANT NOTE: For connections with user-configurable ports assigned, customers can use
the default value or assign a different port number in the range of 1024 to 65534. Connections
using non-default TCP ports are handled by additional Totalflow/TCP communication or Modbus
TCP applications configured with different TCP ports. For example, the figure below shows an
additional Totalflow/TCP application (named ControlGroup) with a different TCP port (10001).

Table of Contents

Related product manuals