SM01P 36
The following input functions can be selected for P12:
01 NONE: Disables the TB-13E function.
02 0-10 VDC: Selects a 0-10 VDC signal (at TB-5) as the AUTO speed reference
input.
03 4-20 mA: Selects a 4-20 mA signal (at TB-25) as the AUTO speed reference input.
04 PRESET SPEED #3: Selects PRESET SPEED #3 as the speed reference. The drive
will operate at the frequency programmed into Parameter 33.
05 INCREASE FREQ: Closing TB-13E to TB-11 will increase the speed setpoint until
the contact is opened. INCREASE FREQ will only work when the drive is running.
TB-13B must be programmed for DECREASE FREQ.
06 START FORWARD: Sets up the drive for a 3-wire start/stop circuit. Momentarily close
TB-13E to TB-11 to start the drive, and momentarily open TB-1 to TB-11 to stop.
07 EXTERNAL FAULT: Sets TB-13E as a normally closed external fault input. Open
TB-13E to TB-11 to trip the drive.
08 INVERSE EXTERNAL FAULT: Sets TB-13E as a normally open external fault input.
Close TB-13E to TB-11 to trip the drive.
09 AUXILIARY STOP: When TB-13E is opened with respect to TB-11, the drive will
decelerate to a STOP (even if STOP METHOD is set to COAST) at the rate set into
ACCEL/DECEL #2 (Parameter 42).
10 ACCEL/DECEL #2: Selects the acceleration and deceleration time programmed into
ACCEL/DECEL #2 (Parameter 42).
The following output functions can be selected for P12. The terms "open" and "close"
refer to the state of the internal transistor that activates the circuit. When the transistor
is "closed" the circuit is complete, and TB-13E is pulled up to 15 VDC (when "open", TB-
13E is at 0 VDC potential).
11 RUN: Closes upon a START command. Opens if the drive is in a STOP state, the
drive faults, or input power is removed. DC braking is considered a STOP state.
12 FAULT: Closes if there is no fault condition. Opens if the drive faults, or input power
is removed.
13 INVERSE FAULT: Closes if the drive faults. Opens if there is no fault condition.
14 FAULT LOCKOUT: Closes when input power is applied. Opens if three restart attempts
are unsuccessful, or if input power is removed.
15 AT SET SPEED: Closes if the drive is within + 0.5 Hz of the speed setpoint.
16 ABOVE PRESET SPEED #3: Closes if the output frequency exceeds PRESET
SPEED #3 (Parameter 33). Opens if the output frequency is equal to or less than
PRESET SPEED #3.
17 CURRENT LIMIT: Closes if the output current exceeds the CURRENT LIMIT setting.
Opens if the output current is equal to or less than CURRENT LIMIT (see Parameter
25).