Kitchen Hoods • Type I and Type II10
Installing Front/Side External Supply Plenums
Using Uni-strut
Uni-strut (supplied by others) supporting the hood may
be cantilevered over the end of the hood. Utilizing the
external supply plenum’s hanger brackets, securely
fasten to the uni-strut.
HOOD STANDING SEAM
HANGING CLIP FASTENED TO PLENUM SHELL
HANGING CLIP
HOOD FRONT
"C" CLAMP
SUPPLY PLENUM SHELL
END VIEW
HOOD
EXTERNAL
SUPPLY
PLENUM
ATTACH HANGING CLIP TO
HOOD STANDING SEAM WITH
THE SUPPLIED "C" CLAMPS
(OPTIONAL: DRILL AND BOLT A
1/4-20 SS BOLT THROUGH
THE CLIP AND HOOD STANDING
SEAM)
HANGING METHODS FOR SUPPLY PLENUMS
ASP, FSP AND VSP
TOP VIEW
HOOD
TOP VIEW
SUPPLY PLENUM
2 CLIPS ARE NEEDED
3 CLIPS ARE NEEDED
FOR PLENUMS > 96 INCHES (243.8 CM)
FOR PLENUMS <= 96 INCHES (243.8 CM)
THE THIRD CLIP IS LOCATED
IN THE CENTER OF THE
PLENUM LENGTH
THREADED ROD
OPTION #1 HANGING CLIP
HANGING CLIP COULD BE 23.5 INCHES (59.69 CM) FROM END IF THERE IS
A UTILITY CABINET ON THE END OF THE HOOD
OPTION #1 = HANGING CLIP
OPTION #2 = UNI-STRUT
OPTION #3 = THREADED ROD
OPTIONAL UTILITY CABINET
NOTE: SUPPLY PLENUMS ARE STANDARDLY SUPPLIED WITH HANGING CLIPS (OPTION 1),
IF OPTION #1 IS NOT APPLICABLE, USE OPTIONS 2 0R 3
SUPPLIED BY OTHERS
UNI-STRUT (U-CHANNEL)
SUPPLIED BY OTHERS
23.5 IN.
(59.69 CM)
11.5 IN.
(29.2 CM)
1. Insert 1/2 in. (12.7 mm) diameter threaded rod (by
others) into hanger brackets on the external supply
plenum top. Raise and hang the external supply
plenum from adequate roof or ceiling supports.
3. It is recommended that caulk be applied at the
mating seams and surfaces of the external supply
plenum, the hood, and the wall. If the external supply
plenum is next to a wall, you will need to caulk
around the surface next to the wall. Caulk the joints
with NSF Approved silicone caulk (GE SCS1009, or
its equivalent). The caulk is not provided.
Installing the Supply Duct Collar to the Plenum
Place the duct collar(s) over the opening, fastening
with tack-welds at 1 to 2 in. (2.54 to 5.08 cm) intervals,
or sheet metal screws at 3 to 6 in. (7.62 to 15.24 cm)
intervals. It is suggested that the duct collar be attached
to the supply plenum before installing the supply
plenum.
2. The external supply plenum should be resting
lightly against the hood. The hood is only used to
position the plenum; it is not intended to support the
plenum. All hanger brackets on the external supply
plenum must be used and the plenum must be
properly supported while lifting to prevent damage or
distortion. The external supply plenum must be level
to operate properly.
NOTE
Ensure the external supply plenum is installed
flush with the hood front and is plumb and level by
adjusting the threaded rod(s). There should be no gap
between the bottom of the external supply plenum
and the hood after installation and adjustments are
completed.
NOTE
After hanging, secure the external supply plenum to
the hood (or to another external supply plenum) using
the supplied turnbuckle(s). Use caution tensioning the
turnbuckle. Too much tension may cause the bottom
of the external supply plenum to pull away from
the hood or cause the face of the hood to become
deformed.
HOOD
EXTERNAL
SUPPLY
PLENUM
EXTERNAL
SUPPLY PLENUM
HANGER BRACKET
EXTERNAL
SUPPLY PLENUM
HANGER BRACKET
UNI-STRUT
(U-CHANNEL)
UNI-STRUT
(U-CHANNEL)
THREADED
ROD
THREADED
ROD
HOOD HANGER
BRACKET
HOOD HANGER
BRACKET
TURNBUCKLE
TURNBUCKLE
Using Hanger Brackets and Threaded Rod
When using the uni-strut (supplied by others), it must be
bolted to the hood and external supply plenum hanger
brackets.
FIG. 9 FIG. 10
FIG. 12 FIG. 13 FIG. 14
FIG. 15
FIG. 16 FIG. 17
FIG. 20 FIG. 23 FIG. 53 FIG. 54 FIG. 55
L (MODULE LENGTH)
L/2
L/2
L/2
L (MODULE LENGTH)
L/4
L/4
FASTENERS HOLDING THE
BACKSUPPLY TO THE WALL
REMOVABLE AIR DIFFUSERS
HEMMED EDGE
FULL END SKIRT
ATTACH TO WALL
FASTENERS BY OTHERS
HOLE DRILLED
BY INSTALLER
1/4 INCH BOLT AND CAP NUT
SUPPLIED BY MANUFACTURER
HOOD FRONT PANEL
HOOD END PANEL
BACKSPLASH PANEL
SLIDE FLANGE
BEHIND BACK
OF THE HOOD
SECTION VIEW
OF BACKSPLASH
PANEL OVERLAP
31.25 INCH
CRITICAL
DIMENSION
Air Curtain
Supply Plenum (ASP)
NOTE
The uni-strut needs to be the full length of the hood
and the external supply plenum.
HOOD
EXTERNAL
SUPPLY
PLENUM
EXTERNAL
SUPPLY PLENUM
HANGER BRACKET
EXTERNAL
SUPPLY PLENUM
HANGER BRACKET
UNI-STRUT
(U-CHANNEL)
UNI-STRUT
(U-CHANNEL)
THREADED
ROD
THREADED
ROD
HOOD HANGER
BRACKET
HOOD HANGER
BRACKET
TURNBUCKLE
TURNBUCKLE
Air Curtain Supply (ASP)
Mounted with uni-strut and threaded rod