SGM3000 Series Smart Meters
User Manual
Restricted
GEH-7111-1.00-2
83
meter automatically clears the Low Potential caution when all active phases exceed the
minimum threshold for two consecutive tests.
8.9.2.6 CA 004 000Demand Overload
The Demand Overload caution indicates that the kW demand exceeded the programmed
threshold. The meter compares the value of the instantaneous kW demand quantity to the
programmed threshold every five seconds using the demand from the previous second. The
meter sets the Demand Overload caution when the kW demand exceeds its threshold for 3
consecutive tests. The meter does not automatically clear the Demand Overload caution. The
Demand Overload caution is cleared by a demand reset.
8.9.2.7 CA 040 000Leading kvarh
The Leading kvarh caution indicates that the current leads the voltage instead of lagging it. The
meter tests the direction of the quadergy every five seconds using the kvarh from the previous
second. The meter sets the Leading kvarh caution when the direction of the quadergy is leading
for three consecutive tests. The meter does not automatically clear the Leading kvarh caution.
The Leading kvarh caution is cleared by a demand reset.
8.9.2.8 CA 400 000Received kWh
The Received kWh caution indicates that active energy was received from the load. The meter
tests the direction of the active energy every five seconds using the kWh from the previous
second. The meter sets the Received kWh caution when the direction of the active energy is
received for three consecutive tests. The meter does not automatically clear the Received kWh
caution. The Received kWh caution is cleared by a demand reset.