SGM3000 Series Smart Meters
User Manual
Table 14 Fault Symptoms Without Codes
High/low demand
registration
a. Terminal wiring error
b. Meter internal wiring defective
c. Defective sensor
a. Rewire according to applicable
diagram.
b. Check that voltage and current
connectors are seated properly. Check
the leads for damage.
c. Replace meter.
a. Meter terminal has insufficient
capacity or is not adequately
wired.
b. Meter is overloaded.
c. Poor connection at terminal
a. Replace mounting with a higher
ampere rated installation.
b. Use transformer rated installation.
c. Redo terminal connections.
a. Terminal wiring error
b. Meter internal wiring defective
c. Defective sensor
a. Rewire according to applicable
diagram.
b. Check that voltage and current
connectors are seated properly. Check
the leads for damage.
c. Replace meter.
a. Circuit de-energized
b. Meter internal wiring defective
a. Check circuit voltages.
b. Check that the voltage and current
sensors are properly connected. Also
check the wires for damage.