The figures for (B) and (C) only apply to type B23
connectors.
Base
The base on which the boiler will be mounted must be made from
non-combustible materials.
CHIMNEY CONNECTIONS
IMPORTANT
The boiler must be installed by a qualified engineer
in accordance with the local standards and codes of
practice.
Thediameterofthechimneymustnotbelessthanthe
diameteroftheboiler'schimneyreducer.
A
B
F
D
C
E
fig. 6 : Boiler ventilation and chimney connection type B23
ChimneyconnectorAlfaS/SV/M/MV:
TypeB23
(fig.6)
The chimney must be connected to the boiler by means of a
metal pipe rising at an angle from the boiler to the chimney.
Achimneyconnectionisrequired.
BOILER ROOM
Important
Never obstruct the ventilation.
Do not store inflammable products in the boiler room.
Avoid storing corrosive products such as paint, solvents, chlorine,
salt, soap or other cleaning products near the boiler.
Accessibility
The boiler room should be big enough to allow easy access to the
boiler. Minimum clearances around the boiler (mm):
- to the front 500
- to the rear 150
- to the sides 100
- above 700
Ventilation
The boiler room must have both low and high level ventilation
(see Fig. 6).
By way of information, the table below gives the minimum
ventilationrequirementsaccordingtoBelgianregulations.
The user must ensure that his boiler room ventilation
complieswithlocalregulations.
INSTALLATIoN
Ventilation
S / SV SV M / MV MV
Fresh air supply min.
m
3
/h
63 - 63 -
High level ventilation (A)
dm
2
1.5 1.5 1.5 1.5
Low level ventilation (B)
dm
2
1.5 - 1.5 -
Draught stabiliser (C)
Ø
80 - 80 -
Chimney
S M
E = 5 m Ø min. F
mm
200 200
E = 10 m Ø min. F
mm
168 168
E = 15 m Ø min. F
mm
152 152
A. High level ventilation
B. Low level ventilation
C. Draught stabiliser
D. Flame inspection window
E. Height of lined chimney
F. himney diameter
Importantnote:
Theabovetableisshownbywayofindicationonlyas
regulationsvaryfromcountrytocountry.
Thehighefficiencyofourboilersmeansthattheflue
gasesexitatlowtemperature.
Theattendantriskofcondensationmaycausedamage
to some chimneys. To avoid this risk we strongly
advisethatyoulinethechimney.
Please contact your installer for further information
aboutchimneylining.
ChimneyconnectorsSV/MV:
TypeCxx
(fig.7, 8 and 9)
C 13 (x) : Concentric / parallel connector with horizontal
terminal.
C 33 (x) : Concentric / parallel connector with vertical
terminal.
C 43 (x) : Concentric / parallel connector for several boilers in
a common chimney.
C 53 (x) : Parallel chimney connector with air intake and flue
gas outlet in different pressure zones (different
locations).
C 63 (x) : Connector for connection to an approved discharge
system
(Netherlands, Germany and Luxembourg only).