ADAM-4000 Series User Manual 144
4015, 4015T
5.1.22 $AAS0
Name Internal Calibration command
Description This command executes internal self-calibration for offset
and gain errors.
Syntax $AAS0(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of the analog input module which is to be calibrated.
S0 is the Internal Calibration command.
(cr) is the terminating character, carriage return (0Dh).
Response !AA(cr) if the command was valid.
?AA(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exist.
! delimiter character indicates a valid command was received.
? delimiter character indicates the command was invalid.
AA (range 00-FF) represents the 2-character hexadecimal
address of the analog input module.
(cr) represents terminating character, carriage return (0Dh).
4015, 4015T
5.1.23 $AAS1
Name Reload Default Calibrating Parameter command
Description Reload factory default calibrating parameter to overwrite
current calibrating parameter.
Syntax $AAS1(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of the analog input module which is to be reloaded.
S1 is the Reload Calibrating Parameter command.
(cr) is the terminating character, carriage return (0Dh).
Response !AA(cr) if the command was valid.
?AA(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exist.
! delimiter character indicates a valid command was received.
? delimiter character indicates the command was invalid.
AA (range 00-FF) represents the 2-character hexadecimal
address of the analog input module.
(cr) represents terminating character, carriage return (0Dh).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech Adam - 4024 and is the answer not in the manual?

Advantech Adam - 4024 Specifications

General IconGeneral
BrandAdvantech
ModelAdam - 4024
CategoryOther
LanguageEnglish

Related product manuals