I/O Modules
3-
2
ADAM 4100 Series User’s Manual
3.1 The common specification of ADAM-4100 I/O series
Communication
z Speeds: support from 1200 to 115K bps
z Max. communication distance: 4000 feet (1.2 km)
z Communication error checking with checksum
z Asynchronous data format:
Advantech protocol: 1 start bit, 8 data bits, 1 stop bit, no parity
Modbus protocol: 1 start bit, 8 data bits, 1 or 2 stop bit,
parity check (none, odd, even)
z Up to 256 multidrop modules per serial port
z Online module insertion and removal
z Transient suppression on RS-485 communication lines
z Reset default setting
z Power and communication LED indicators
Environmental
z Operating Temperature -40 ~ 85° C (-40 ~ 185° F)
z EMI Meets FCC Class A and CE
z Storage Temperature -40 ~ 85° C (-40 ~ 185° F)
z Humidity 5 ~ 95%, non-condensing
z EFT : 3kV
z ESD : 8KV
Power Requirements
z Unregulated +10 ~ +48 VDC
z Surge Protection: 1kV
Mechanical
z Case ABS & PC with captive mounting hardware
z Plug-in screw terminal block accepts cable #14~28 AWG (0.32 ~1.63
mm2)