Chapter 4
Chapter 4 Command Set
4-61
4.6.22
$AA5NS
Name Start/Stop Counter
Description Request the counter/frequency module to start or stop the
counting for counter 0 or 1.
Syntax $AA5NS(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address which is to be accessed.
5 identifies the Start/Stop Counter command
N determines whether the counter should be enabled or
disabled.
N = 0 represents counter 0
N = 1 represents counter 1
S represents the counter status.
S = 0 stops counting
S = 1 starts counting
(cr) is the terminating character, carriage return (0Dh)
Response !AA(cr) if the command is valid. There is no response if the
module detects a syntax or communication error, or even if
the specified address does not exist.
! is a delimiter character indicating that the command was
valid.
AA (range 00-FF) represents the 2-character hexadecimal
address of a counter input module.
(cr) is the terminating character, carriage return (0Dh).
Example command: $06501(cr)
response: !06(cr)
The command requests the counter/frequency module at
address 06 to start counter 0. The module replies with its
address indicating that the command has been executed and
counter 0 has started.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech ADAM 4100 and is the answer not in the manual?

Advantech ADAM 4100 Specifications

General IconGeneral
BrandAdvantech
ModelADAM 4100
CategoryRecording Equipment
LanguageEnglish