Digital Ground Resistance Tester Model 4500
33
Where:A=distancebetweentheelectrodesincentimeters
B=electrodedepthincentimeters
If A > 20 B, the formula becomes:
ρ=2πAR(withAincm)
ρ=191.5AR(withAinfeet)
ρ=Soilresistivity(ohm-cm)
This value is the average resistivity of the ground at a depth equivalent to
the distance “A” between two electrodes.
Figure 18
4.9
Soil Resistivity Measurement Procedure (4-Point)
Given a sizeable tract of land in which to determine the optimum soil resis-
tivity,someintuitionisinorder.Assumingthattheobjectiveislowresis-
tivity, preference should be given to an area containing moist loam as
opposed to a dry sandy area. Consideration must also be given to the
depth at which resistivity is required.