28
Digital Ground Resistance Tester Model 4500
either side of the initial Y setting are most likely to be within the established
toleranceband.Thistolerancebandisdenedbytheuserandexpressed
as a percent of the initial reading: ± 2%, ± 5%, ± 10%, etc.
Resistance
Current
Electrode
D
62% of D
Resistance of
Auxiliary Current
Electrode
Resistance of Earth Electrode
Figure 14
4.4.1 Auxiliary Electrode Spacing
NodenitedistancebetweenXandZcanbegiven,sincethisdistanceis
relative to the diameter of the electrode tested, its length, the homogeneity
of the soil tested, and particularly, the effective resistance areas. However,
an approximate distance may be determined from the following chart
which is given for a homogeneous soil and an electrode of 1" in diameter.
(For a diameter of 1/2", reduce the distance by 10%; for a diameter of 2"
increasethedistanceby10%.)
Approximatedistancetoauxiliaryelectrodesusingthe62%method:
Depth Driven Distance to Y Distance to Z
6 ft. 45 ft. 72 ft.
8 ft. 50 ft. 80 ft.
10 ft. 55 ft. 88 ft.
12 ft. 60 ft. 96 ft.
18 ft. 71 ft. 115 ft.
20 ft. 74 ft. 120 ft.
30 ft. 86 ft. 140 ft.