EasyManua.ls Logo

AEMC 5600 - Battery Strap Measurements

AEMC 5600
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Micro-Ohmmeter Model 5600
Battery Strap Measurements
Proper battery strap resistance measurements will help ensure proper
voltage output. The resistance on battery strap connections should be
measured using the Kelvin probes (see Figure 9). Measurements must
be made with the system power turned off.
The average resistance of all the intercell connections should be
determined by totaling the individual resistances and dividing by the
number of connectors. Each individual cell resistance should not exceed
the average by more than 10%. See the manufacturer's specifications for
typical resistance values.
C
2
P
2
C
1
P
1
Rx
MICRO-OHM
!
F1
– I
Battery Battery
®
INSTRUMENTS
Figure 9
- 16 -