Modulex MLX Series Gas Fired Boiler System
Operation and Maintenance Manual
Chap 10:
Troubleshooting
FAULT
INDICATION
PROBABLE
CAUSES
CORRECTIVE ACTION
E90:
E8: BUS
addresses 0 and 1
both used. BUS
address 0 and 1
may not be used
simultaneously.
Bus setting incorrect. Change setting to use only one bus.
E91:
E8: BUS ID
already used. The
set BUS ID is
already in use by
another device.
BMM rotary switches
improperly set
duplicate address
settings.
Select unused BUS ID address for device.
E99:
E8: Internal failure
E-8 failure Replace the E-8
E200:
E8: Complete
communication
loss to/from the
E8 such as would
occur when the
three way switch is
flipped to BCM
control
1. bcm three-way
switch is in the
wrong position
(zero position)
2. Loose e-buss
connection (pink
and grey wires)
1. E200 fault is normal when the BMC is control by an
outside source using Modbus. (BMS II or EMS/BAS)
2. Check connection or replace harness.
E201:
E8:
Communication
Error Module 1
BMM Board failure.
BMM Board harness
failure
Check with Desmond
E202:
E8:
Communication
Error Module 2
Same as E201
BMM Board failure.
BMM Board harness
failure
Check with Desmond
Table 10-1: Boiler Troubleshooting System Manager Defective Sensor (Cont.)