17
English
COOLING CAPACITY
FCX 17
TOTAL COOLING CAPACITY [W] SENSIBLE COOLING CAPACITY [W]
Wet bulbe air temperature [°C] Dry bulbe air temperature [°C]
Water temp.
Inlet [°C]
t 15 17 19 21 23 21 23 25 27 29 31
3 884 1246 1624 2012 2428 723 857 996 1112 1226 1337
4 750 1071 1472 1866 2286 652 768 907 1044 1161 1276
5 5 699 920 1277 1710 2137 615 718 820 956 1093 1211
6 852 1105 1525 1975 583 685 781 877 1011 1145
7 1027 1328 1803 548 652 747 835 933 1068
3 777 1109 1495 1882 2299 654 786 923 1054 1170 1282
4 674 934 1328 1734 2157 595 711 840 980 1104 1220
6 5 627 823 1141 1572 2002 562 666 768 895 1029 1155
6 768 991 1364 1833 530 635 731 823 945 1086
7 927 1191 1638 498 601 699 791 879 1001
3 671 964 1362 1750 2167 589 727 858 995 1113 1226
4 602 825 1171 1595 2021 544 652 780 911 1046 1163
7 5736 1000 1403 1859 512 615 716 830 966 1096
6 891 1209 1684 480 580 683 777 879 1018
7 837 1075 1466 447 548 649 744 832 936
3 597 845 1212 1615 2031 532 658 796 930 1054 1168
4 551 718 1036 1452 1879 493 595 717 849 982 1105
8 5 660 875 1252 1710 461 562 667 769 899 1038
6 807 1061 1505 429 530 634 730 822 954
7 970 1296 395 497 600 695 788 878
3 539 727 1055 1472 1889 477 594 728 859 995 1110
4 500 635 900 1282 1730 443 544 654 784 912 1046
9 5 593 775 1098 1555 411 512 614 715 835 969
6 725 941 1346 378 479 579 682 771 891
7 878 1146 345 446 548 649 739 827
3 481 630 920 1309 1744 425 536 662 797 930 1053
4 575 779 1118 1578 392 493 594 722 851 982
10 5 694 955 1378 360 461 561 665 773 903
6 843 1177 326 429 530 631 725 828
7 – 1023 292 395 497 600 694 782
3 429 572 788 1152 1591 374 479 598 731 860 993
4 525 679 982 1405 342 443 543 659 787 918
11 5 622 829 1205 310 410 510 614 716 839
6 757 1027 275 378 479 579 678 770
7 918 238 344 446 547 648 737
3 514 679 986 1432 324 425 541 665 798 928
4 473 600 845 1227 292 392 492 595 725 853
12 5 730 1045 258 360 461 561 664 778
6 891 222 326 428 528 630 723
7 826 182 292 395 497 599 693
3 456 605 856 1259 273 374 483 602 732 858
4 547 732 1071 240 341 442 542 664 789
13 5 654 904 206 309 410 510 614 720
6 795 167 275 377 479 578 678
7 120 238 343 446 547 648
NB: Values of capacity in bold face refer to nominal value.
Values of sensible capacity higher than values of total capacity mean that cooling is without dehumidification. In this case consi-
der only the values of sensible capacity.
The cooling capacities in the table must be multiplied by the following factors:
MOD. FCX 17
Maximun speed
total capacity
1,00
sensible capacity
1,00
Medium speed
total capacity
0,89
sensible capacity
0,86
Minimum speed
total capacity
0,72
sensible capacity
0,65