32
English
0
15
30
45
60
140 155 170 185 200 215 230 245 260 275 290
L1
L2
L3
L4
L5
L6
L7
Air flow rate [m
3
/h]
IPO series fancoils have been designed to adjust available sta-
tic pressure provided by the fan to pressure drop in the ducting
system by selecting the appropriate operating speed.
Tables give the available static pressure of machines fitted with
multiple-speed extra-strength motors, according to air flow and
fan speed (L1...L7).
The diagrams also illustrate the available static pressure curves
of models with standard motors (P-PE) operating at maximum
and medium speed.
L1: max. speed PO version max. speed P version
L7: min. speed PO version average speed P version
Av.Stat.pressure [Pa]
HANGING VERSION AVAILABLE STATIC PRESSURE
FCX 22 - 24
0
15
30
45
60
260
275 290 305 320 335 350 365 380
395
410
425 440 455
L2
L1
L4
L3
L6
L5
L7
Air flow rate [m
3
/h]
Av.Stat.pressure [Pa]
FCX 32 - 34
0
15
30
45
60
75
330 355 380 405 430 455 480 505 530 555 580 605
L1
L2
L3
L4
L7
L6
L5
Air flow rate [m
3
/h]
Av.Stat.pressure [Pa]
FCX 42 - 44
0
10
20
30
40
50
60
400 430 460 490 520 550 580 610 640 670 700 730
L3
L1
L4
L2
L5
L6
Air flow rate [m
3
/h]
Av.Stat.pressure [Pa]
FCX 50 - 54
0
20
40
60
80
520 560 600 640 680 720 760 800 840 880 920
L2
L3
L4
L5
L7
L6
L1
Air flow rate [m
3
/h]
Av.Stat.pressure [Pa]
FCX 62 - 64
0
20
40
60
700 740 780 820 860 900 940 980 1020 1060 1100 1140
L1
L2
L3
L4
L5
L6
L7
Air flow rate [m
3
/h]
Av.Stat.pressure [Pa]
FCX 82 - 84
0
20
40
60
900 940 980 1020 1060 1100 1140 1180 1220 1260 1300
Air flow rate [m
3
/h]
Av.Stat.pressure [Pa]
FCX 102 (only P)