12
English
TECHNICAL DATA
Performance values refer to the following conditions:
Sound pressure measured in an 85 m
3
semi-reverberant test
chamber with reverberation time Tr = 0.5s.
Cooling:
- room air temperature 27 °C B.S., 19 °C B.U.;
• maximum speed:
- water inlet temperature 7 °C; ∆t water 5 °C.
• medium and low speed:
- water inlet temperature 7 °C;
- water flow rate remains same as at maximum speed.
Heating:
room air temperature 20 °C B.S.;
• maximum speed:
- water inlet temperature 70 °C; ∆t water 10 °C;
• medium and low speed:
- water inlet temperature 70 °C;
- water flow rate remains same as at maximum speed.
• maximum speed (water inlet 50°C):
- water inlet temperature 50 °C;
- water flow rate same as in cooling operation.
FCX 17 FCX 22 FCX 32 FCX 42 FCX 50 FCX 62 FCX 82 FCX 102
2490 3400 4975 7400 8620 12920 15140 17020
2070 2700 4085 6415 7530 10940 13350 15240
1610 1915 3380 5115 5420 8330 10770 12560
1360 2100 3160 4240 4900 6460 7990 9670
700 950 1300 1650 1950 2200 2200 2200
214 292 427 636 741 1110 1300 1464
2,8 6,3 14,2 14,1 14,2 14,8 19,8 16,6
1000 1500 2210 3400 4190 4860 7420 7620
890 1330 2055 2800 3640 4660 5500 7140
720 1055 1570 2310 2840 3950 4710 6270
830 1240 1750 2760 3000 3980 5680 5980
710 1055 1540 2115 2750 3510 4250 4984
540 755 1100 1635 2040 2825 3450 4263
172 258 380 585 721 836 1276 1311
2,6 5,8 16,6 14,3 19,3 11,6 13,5 19,2
200 290 450 600 720 920 1140 1300
160 220 350 460 600 720 930 1120
110 140 260 330 400 520 700 900
1 1 2 2 2 3 3 3
36,5 41,5 39,5 42,5 47,5 48,5 53,5 57,5
29,5 34,5 32,5 35,5 42,5 42,5 48,5 52,5
22,5 22,5 25,5 28,5 33,5 33,5 41,5 47,5
45 50 48 51 56 57 62 66
38 43 41 44 51 51 57 61
31 31 34 37 42 42 50 56
0,58 0,79 1,11 1,48 1,48 2,52 2,52 2,52
35 25 44 57 67 82 106 131
0,16 0,12 0,21 0,28 0,35 0,40 0,49 0,58
735 975 1344 1707 2017 2282 2306 2331
3,2 4,25 5,86 7,45 8,83 9,97 10,06 10,15
1/2” 1/2” 1/2” 3/4” 3/4” 3/4” 3/4” 3/4”
1/2” 1/2” 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
Mod.
Heating
W (max.)
Heating capacity W (med.)
W (min.)
Heating capacity*
W (E)
(water inlet 50°C)
Heating capacity (accessory RX) W
Water flow rate l/h
Water pressure drop kPa
Cooling
W (max.) (E)
Total cooling capacity W (med.)
W (min.)
W (max.) (E)
Sensible cooling capacity W (med.)
W (min.)
Water flow rate l/h
Water pressure drop kPa (E)
m
3
/h (max.)
Air flow rate m
3
/h (med.)
m
3
/h (min.)
Fans n.
dB (A) (max.)
Sound pressure dB (A) (med.)
dB (A) (min.)
dB (A) (max.) (E)
Sound power dB (A) (med.) (E)
dB (A) (min.) (E)
Water contents l
Max. motor power W (E)
Max. input current A
Max. motor power
W
with electric heater
Input current
A
with electric heater
Coil connections 3R ø
Coil connections 1R ø
FCX A-AS-ACT-APC-ACB-U-P with 3-row coil
Power supply = 230V ~ 50Hz (E) = EUROVENT certified performance