HEATING POWER YIELD 3-ROW COIL
HEATING CAPACITY CORRECTION FACTORS
The heating capacities are at maximum speed. For the other speeds, the values must be multiplied by the following factors:
MOD. FCX17 FCX 22 FCX 32 FCX 42 FCX 50 FCX 62 FCX 82 FCX102
Medium speed 0,83 0,79 0,82 0,87 0,87 0,85 0,88 0,90
Low speed 0,65 0,56 0,68 0,69 0,63 0,64 0,71 0,74
4 6 8 101214161820
300
600
900
1200
1500
1800
20
40
50
30
60
70
2100
22
Water flow rate (l/h)
∆t °C (temperature entering water - temperature entering air)
Heating capacity [kW]
FCX 82
600
800
1000
1200
1400
1600
1800
2000
2200
5 7 9 1113151719212325
Water flow rate (l/h]
∆t °C (temperature entering water - temperature entering air)
Heating capacity [kW]
FCX 102