1-ROW COIL HEATING CAPACITY (ACCESSORY BV)
HEATING CAPACITY CORRECTION FACTORS
The heating capacities are at maximum speed. For the other speeds, the values must be multiplied by the following factors:
MOD. FCX17 FCX 22 FCX 32 FCX 42 FCX 50 FCX 62 FCX 82 FCX102
Medium speed 0,89 0,85 0,86 0,88 0,89 0,86 0,9 0,91
Low speed 0,73 0,64 0,72 0,68 0,74 0,71 0,76 0,81
The 3- row coil heating capacity in the fancoil quipped with BV coil accessory ( 3R + 1R lay-out) are detected by the charts /
graphs relating to the 3-row standard coil by applying the here below coefficients.
Total cooling capacity = 0,99
Sensible cooling capacity = 0,98