13
English
TECHNICAL DATA
Performance values refer to the following conditions:
Sound pressure measured in an 85 m
3
semi-reverberant test chamber
with reverberation time Tr = 0.5s.
Cooling:
- room air temperature 27 °C B.S., 19 °C B.U.;
• maximum speed:
- water inlet temperature 7 °C; t water 5 °C.
• medium and low speed:
- water inlet temperature 7 °C;
- water flow rate remains same as at maximum speed.
Heating:
room air temperature 20 °C B.S.;
• maximum speed:
- water inlet temperature 70 °C; t water 10 °C;
• medium and low speed:
- water inlet temperature 70 °C;
- water flow rate remains same as at maximum speed.
• maximum speed (water inlet 50°C):
- water inlet temperature 50 °C;
- water flow rate same as in cooling operation.
FCX 22 FCX 32 FCX 42 FCX 50 FCX 62 FCX 82
3400 4975 7400 8620 12920 15140
2700 4085 6415 7530 10940 13350
1915 3380 5115 5420 8330 10770
2100 3160 4240 4900 6460 7990
950 1300 1650 1950 2200 2200
292 427 636 741 1110 1300
6,3 14,2 14,1 14,2 14,8 19,8
1500 2210 3400 4190 4860 7420
1330 2055 2800 3640 4660 5500
1055 1570 2310 2840 3950 4710
1240 1750 2760 3000 3980 5680
1055 15
40 2115 2750 3510 4250
755 1100 1635 2040 2825 3450
258 380 585 721 836 1276
5,8 16,6 14,3 19,3 11,6 13,5
290 450 600 720 920 1140
220 350 460 600 720 930
140 260 330 400 520 700
1 2 2 2 3 3
41,5 39,5 42,5 47,5 48,5 53,5
34,5 32,5 35,5 42,5 42,5 48,5
22,5 25,5 28,5 33,5 33,5 41,5
50 48 51 56 57 62
43 41 44 51 51 57
31 34 37 42 42 50
0,79 1,11 1,48 1,48 2,52 2,52
54 97 111 82 97 135
0,25 0,45 0,51 0,36 0,48 0,62
1004 1397 1761 2032 2297 2335
4,38 6,00 7,68 8,84 10,05 10,19
1/2” 1/2” 3/4” 3/4” 3/4” 3/4”
1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
Mod.
Heating
W (max.)
Heating capacity W (med.)
W (min.)
Heating capacity*
W (E)
(water inlet 50°C)
Heating capacity (accessory RX) W
Water flow rate l/h
Water pressure drop kPa
Cooling
W (max.) (E)
Total cooling capacity W (med.)
W (min.)
W (max.) (E)
Sensible cooling capacity W (med.)
W (min.)
Water flow rate l/h
Water pressure drop kPa (E)
m
3
/h (max.)
Air flow rate m
3
/h (med.)
m
3
/h (min.)
Fans n.
dB (A) (max.)
Sound pressure dB (A) (med.)
dB (A) (min.)
dB (A) (max.) (E)
Sound power dB (A) (med.) (E)
dB (A) (min.) (E)
Water contents l
Max. motor power W
Max. input current A
Max. motor power
W
with electric heater
Input current
A
with electric heater
Coil connections 3R ø
Coil connections 1R ø
FCX PO with 3-row coil
Power supply = 230V ~ 50Hz (E) = EUROVENT certified performance

Other manuals for AERMEC FCX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC FCX and is the answer not in the manual?

AERMEC FCX Specifications

General IconGeneral
BrandAERMEC
ModelFCX
CategoryHousehold Appliance
LanguageEnglish

Related product manuals