23
English
COOLING CAPACITY
FCX 82
The cooling capacities in the table must be multiplied by the following factors:
MOD. FCX 82 FCX 84
Maximum speed
total capacity
1,00 1,24
sensible capacity
1,00 1,06
Medium speed
total capacity
0,80 1,10
sensible capacity
0,85 1,00
Low speed
total capacity
0,68 0,91
sensible capacity
0,69 0,80
TOTAL COOLING CAPACITY [W] SENSIBLE COOLING CAPACITY [W]
Wet bulbe air temperature [°C] Dry bulbe air temperature [°C]
Water temp.
Inlet [°C]
∆t 15 17 19 21 23 21 23 25 27 29 31
3 5591 7373 – – – 4995 5671 6366 7036 7680 8303
4 4979 6701 8676 10810 0 4612 5326 6023 6722 7409 8055
5 5 4320 5975 7952 10144 12453 4127 4927 5664 6367 7082 7760
6 3553 5167 7131 9381 11749 3569 4400 5232 5983 6715 7440
7 3291 4225 6243 8503 10985 3346 3939 4689 5556 6331 7069
3 4979 6688 – – – 4656 5338 6008 6699 7344 7987
4 4427 6014 7965 10106 – 4262 4990 5672 6373 7073 7735
6 5 3815 5315 7212 9401 11729 3710 4576 5313 6019 6732 7428
6 3217 4549 6405 8597 10985 3248 3978 4879 5643 6357 7085
7 3008 3782 5517 7696 10164 3032 3658 4291 5193 5969 6718
3 4427 6002 7925 – – 4318 4996 5669 6354 7018 7657
4 3930 5369 7218 9361 – 3890 4652 5337 6011 6723 7401
7 5 3392 4710 7420 8638 10966 3256 4211 4972 5680 6381 7084
6 2927 3984 5705 7803 10203 2934 3591 4504 5290 6015 6742
7 2725 3432 4817 6902 9342 2718 3346 3953 4818 5619 6367
3 3949 5342 7185 – – 3950 4670 5337 5999 6679 7324
4 3526 4763 6486 8611 10887 3480 4310 5009 5681 6364 7056
8 5 3210 4159 5773 7830 10183 2852 3815 4624 5337 6022 6740
6 2645 3473 5033 6997 9381 2621 3248 4115 4938 5668 6380
7 – 3143 4172 6136 8477 2405 3032 3651 4427 5263 6006
3 3566 4724 6432 – – 3555 4340 5002 5654 6329 6978
4 3156 4219 5786 7803 10106 3054 3942 4671 5347 6008 6711
9 5 2585 3687 5113 7024 9361 2532 3375 4275 4996 5688 6375
6 – 3096 4414 6230 8503 2308 2934 3674 4588 5320 6032
7 – 2861 3648 5382 7589 2083 2718 3346 4008 4898 5660
3 3210 4192 5719 7723 – 3151 3971 4678 5336 5978 6644
4 2773 3762 5113 6997 9283 2599 3539 4340 5017 5686 6356
10 5 – 3291 4508 6270 8503 2219 2905 3898 4668 5357 6034
6 – 2780 3875 5503 7642 1995 2621 3271 4219 4984 5694
7 – – 3284 4697 6754 1770 2405 3032 3666 4538 5315
3 2847 3755 5046 6916 – 2741 3576 4355 4997 5647 6300
4 – 3392 4522 6230 8450 2136 3114 3986 4692 5357 6000
11 5 – 2894 3984 5530 7628 1905 2532 3472 4329 5026 5694
6 – – 3405 4831 6808 1679 2308 2934 3808 4650 5351
7 – – 2995 4077 5948 1442 2088 2718 3346 4132 4968
3 – 3405 4448 6136 – 2323 3181 3994 4679 5326 5953
4 – 3015 4003 5503 7562 1811 2681 3584 4370 5026 5671
12 5 – – 3553 4871 6781 1589 2219 3017 3971 4704 5369
6 – – 2988 4239 6002 1358 1995 2621 3346 4297 5026
7 – – – 3539 5194 1103 1770 2405 3032 3718 4617
3 – 3049 3957 5402 7440 1868 2774 3599 4365 4995 5622
4 – – 3600 4831 6727 1495 2196 3166 4024 4713 5348
13 5 – – 3176 4293 5988 1270 1905 2554 3547 4372 5038
6 – – – 3728 5275 1025 1679 2308 2949 3915 4691
7 – – – 3156 4535 732 1444 2088 2718 3346 4254
NB: Values of capacity in bold face refer to nominal value.
Values of sensible capacity higher than values of total capacity mean that cooling is without dehumidification. In this case consi-
der only the values of sensible capacity.